Parameter Group
-314-
Min.:
0.0
Unit:
s
Max.:
300.0
Data type: UInt16
Default:
20.0
Change:
At once
Value Range:
0.0s to 300.0s
Description
This parameter is valid only in the "decelerate to stop" mode (F9-59 = 2).
When the bus voltage is lower than the value of F9-62, the AC drive decelerates to stop. The
deceleration time is determined by this parameter but not F0-18.
2.11 FA: Process Control PID Function
FA-00
PID reference source
Address:
64000
Min.:
0
Unit:
-
Max.: 6 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Digital setting of PID (FA-01)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication
6: Multi-reference
Description
This parameter specifies the PID reference source. The PID reference is a relative value. The value
100% corresponds to 100% of the feedback signal of the controlled system.
0: Digital setting of PID (FA-01)
The PID reference is set by FA-01 (PID reference value).
1: AI1
The PID reference source is the AI1 input.
2: AI2
The PID reference source is the AI2 input.
3: AI3
The PID reference source is the AI2 input.
5: Communication
The PID reference is set by remote communication.
6: Multi-reference
In the multi-reference mode, different combinations of DI terminal states correspond to different
frequency references. The four multi-reference terminals provide 16 state combinations,
corresponding to 16 target frequency values. Note: When FA-00 is set to 6 (multi-reference), FC-51
(reference 0 source) cannot be set to 5 (PID reference).
FA-01
Digital setting of PID
Address:
64001
Min.:
0.0
Unit:
%
Max.:
100.0
Data type:
UInt16