Function Applications
-511-
The AC drive provides two groups of current detection level and width parameters. The following figure
shows the timing diagram.
Figure 4-63 Current detection timing diagram
Related Parameters
Para. No. Name
Default
Value Range Description
F8-42
Detection level
of current 1
100.0%
0.0% to 300.0%
(rated motor
current)
When the output current of the AC drive is
within the range of [F8-42 (detection level of
current 1)±F8-43 (detection width of current
1)] x F1-03 (rated motor current), the DO
terminal outputs an active signal.
F8-43
Detection width
of current 1
0.0%
0.0% to 300.0%
(rated motor
current)
Detection width of current 1 = F8-43 (detection
width of current 1) x F1-03 (rated motor
current)
F8-44
Detection level
of current 2
100.0%
0.0% to 300.0%
(rated motor
current)
When the output current of the AC drive is
within the range of [F8-44 (detection level of
current 2)±F8-45 (detection width of current
2)] x F1-03 (rated motor current), the DO
terminal outputs an active signal.
F8-45
Detection width
of current 2
0.0%
0.0% to 300.0%
(rated motor
current)
Detection width of current 2 = F8-45 (detection
width of current 2) x F1-03 (rated motor
current)
4.5.2 FWD/REV Switchover Dead-zone Time
FWD/REV switchover dead-zone time (F8-13) indicates the transition time at 0 Hz output during
transition between forward running and reverse running of the AC drive.
Figure 4-64 FWD/REV switchover dead-zone time