Software Tools
-416-
Para. No. Name
Default
Value Range Description
FP-02
Parameter display
111
Ones: Group U
0: Hide
1: Display
Tens: Group A
0: Hide
1: Display
Hundreds: Group B
0: Hide
1: Display
Thousands: Group C
0: Hide
1: Display
This parameter is used to determine whether to display
the parameters of groups U, A, B, and C on the operating
panel.
FP-03
Individualized
parameter display
mode
0
Ones:
0: Hide
1: Display
Tens:
0: Hide
1: Display
This parameter is used to determine whether to display
the user-customized parameter group and the user-
modified parameter group on the operating panel.
3.1.3 Setting Parameters
The operating panel adopts the following three-level menu to perform operations such as parameter
settings:
● Level I: parameter group
● Level II: parameter No.
● Level III: parameter setting value
After entering the menu, you can press
,
, and
to modify the blinking bit on the
operating panel.
Example: changing the value of F3-02 from 10.00 Hz to 15.00 Hz