2.9 F8: Auxiliary Functions
F8-00
Jog frequency
Address:
63488
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
2.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
This parameter defines the running frequency of the AC drive in the jogging mode.
F8-01
Jog acceleration time
Address:
63489
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
20.0
Change:
At once
Value Range:
0.0s to 6500.0s
Description
This parameter defines the acceleration time of the AC drive in the jogging mode.
F8-02
Jog deceleration time
Address:
63490
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
20.0
Change:
At once
Value Range:
0.0s to 6500.0s
Description
This parameter defines the deceleration time of the AC drive in the jogging mode.
F8-03
Acceleration time 2
Address:
63491
Min.:
0.0
Unit:
s
Max.:
6500.0
Data type:
UInt16
Default: Model dependent Change:
At once
Value Range:
0.0s to 6500.0s
Description
The AC drive provides four groups of acceleration time, which can be switched by using the DI
terminal. This parameter defines the second group of acceleration time.