Parameter Group
-321-
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Disabled
1: Enabled
Description
0: Disabled When integral pause is disabled, it remains inactive no matter whether the multi-
functional DI is active.
1: Enabled When integral pause is enabled, the PID integral operation stops when the DI assigned
with the PID integral pause function is active (F4-00 = 22 for example). In this case, only PID
proportional and derivative actions are active.
FA-26
Detection level of PID feedback loss
Address:
64026
Min.:
0.0
Unit:
%
Max.: 100.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0% to 100.0%
Description
This parameter is used to determine whether the PID feedback is lost. When the PID feedback remains
lower than the value of FA-26 (PID feedback loss detection value) for longer than the time set by FA-27
(PID feedback loss detection time), the AC drive reports E31.00.
The setpoint 0 indicates that detection on feedback loss is disabled.
FA-27
Detection time of PID feedback loss
Address:
64027
Min.:
0.0
Unit:
s
Max.:
20.0
Data type:
UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 20.0s
Description
This parameter is used to determine whether the PID feedback is lost. When the PID feedback remains
lower than the value of FA-26 (PID feedback loss detection value) for longer than the time set by FA-27
(PID feedback loss detection time), the AC drive reports E31.00.
2.12 FB: Wobble, Fixed Length, and Count
FB-00
Wobble setting mode
Address:
64256
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Relative to center frequency
1: Relative to maximum frequency