Parameter Group
-53-
Ones: DO1/RO1 active mode
Tens: DO2/RO2 active mode
Hundreds :DO3/RO3 active mode
Thousands: DO4/RO4 active mode
Ten thousands: DO5/RO5 active mode
0: Active high
1: Active low
Description
When active high is selected, the DO/RO terminal is active when connected to COM and inactive when
disconnected from COM.
When active low is selected, the DO/RO terminal is inactive when connected to COM and active when
disconnected from COM.
F5-21
Circuit breaker action threshold
Address:
62741
Min.:
0
Unit:
V
Max.: 1000 Data type: UInt16
Default:
Three-phase 380 V: 570 V Single-
phase 220 V: 330 V
Change:
At once
Value Range:
0 V to 1000 V
Description
This parameter defines the circuit breaker action threshold.
1.5 FA: Fault Log Query
FA-00
Fault code of the 5th fault (latest)
Address:
64000
Min.:
0
Unit:
-
Max.: 0 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
-
Description
Fault code of the 5th fault (latest)
FA-01
Fault subcode of the 5th fault
Address:
64001
Min.:
0
Unit:
-
Max.:
0
Data type:
UInt16
Default:
0
Change: Unchangeable
Value Range:
-
Description
Fault subcode of the 5th fault
FA-02
Bus voltage upon the 5th fault
Address:
64002
Min.:
0.0
Unit:
V