Parameter Group
-348-
Description
This parameter is used to determine whether to display the user-customized parameter group and
the user-modified parameter group on the operating panel.
FP-04
Parameter modification
Address:
7940
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Modification allowed
1: Modification prohibited
Description
This parameter defines whether the user password can be modified.
2.17 A0: Torque Control and Limit Parameters
A0-00
Speed/Torque control mode
Address:
40960
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Speed control
1: Torque control
Description
Two control modes are provided under vector control: speed control and torque control.
A0-01
Torque reference source
Address:
40961
Min.:
0
Unit:
-
Max.: 7 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Digital setting (A0-03)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication (1000H)
6: Min. (AI1, AI2)
7: Max. (AI1, AI2)
Description
This parameter defines the torque reference source. There are a total of seven torque reference
sources.
A0-03
Torque digital setting
Address:
40963
Min.:
-2.000
Unit:
%