Parameter Group
-259-
The curves for AI1 to AI3 are set through the ones, tens, and hundreds of this parameter. You can
select any AI curve for each AI.
1: Curve 1 (2 points)
Two-point curve. The relationship between the voltage and frequency is set by F4-31 to F4-34.
1: Curve 2 (2 points)
Two-point curve. The relationship between the voltage and frequency is set by F4-35 to F4-38.
3: Curve 3 (2 points)
Two-point curve. The relationship between the voltage and frequency is set by F4-39 to F4-42.
4: Curve 4 (4 points)
Four-point curve. The relationship between the voltage and frequency is set by F6-00 to F6-07.
4: Curve 4 (4 points)
Four-point curve. The relationship between the voltage and frequency is set by F6-08 to F6-15.
F4-49
Setting for AI lower than minimum input
Address:
62513
Min.:
0
Unit:
-
Max.: 111 Data type: UInt16
Default:
0
Change:
At once
Value Range:
Ones:
0: Percentage corresponding to minimum input
1: 0.0%
Tens:
0: Percentage corresponding to minimum input
1: 0.0%
Hundreds:
0: Percentage corresponding to minimum input
1: 0.0%
Description
The settings for AI1 to AI3 less than the minimum input are set through the ones, tens, and hundreds
of this parameter.
0: Percentage corresponding to minimum input
When the AI input is lower than the minimum setting value, the frequency is calculated based on the
minimum input.
1: 0.0%
When the AI input is lower than the minimum setting value, the frequency is calculated based on the
AI input being 0.0%.
2.6 F5: Output Terminals
F5-00
DO1/RO1 hardware source
Address:
62720
Min.:
0
Unit:
-
Max.: 208 Data type: UInt16
Default:
0
Change:
At once
Value Range: