Function Applications
-506-
F0-09 defines the running direction of the motor. You can change the rotation direction of the motor by
modifying this parameter without changing the motor wiring. Modifying this parameter is equivalent to
exchanging any two of the motor's U, V, W wires.
Note
After the parameter is initialized, the original rotation direction of the motor is resumed. Exercise cautions when us-
ing this function if motor rotation direction change is prohibited after system commissioning is complete.
Figure 4-57 Reverse frequency inhibition
Related Parameters
Para. No. Name
Default
Value Range Description
F8-14
Reverse running
0
0: Reverse running
allowed
1: Reverse running
inhibited
When F8-14 is active, the motor runs at
zero frequency when a reverse run
command is input to the AC drive.
F0-09
Running
direction
0
0: Default direction
1: Direction opposite to
the default direction
You can change the rotation direction
of the motor by modifying this
parameter without changing the motor
wiring. Modifying this parameter is
equivalent to exchanging any two of
the motor's U, V, W wires.
4.5.2.5 Frequency Detection Range
F8-26 defines the frequency detection range. The following figure shows the timing diagram of the
frequency detection range.