Function Applications
-423-
4 Function Applications
4.1 Drive Configuration
4.1.1 Operation Command Sources
4.1.1.1 Setting Operation Command Source
Operation commands are used to control the start, stop, forward run, reverse run, and jog operations
of the AC drive. Three operation command sources are available: operating panel, terminals, and
communication. You can select the operation command source by setting F0-02.
Para. No. Name
Default
Value Range Description
F0-02
Operation
command source
0
0: Operating panel
control
1: Terminal I/O
control
2: Communication
control
This parameter defines the source of the AC
drive control commands, such as run, stop,
forward run, reverse run, and jog.
0: Operating panel control
When this command source is selected,
control commands are input by using
(RUN key), (stop command/fault
reset key), and
(multi-function key)
on the operating panel. It applies to initial
commissioning.
1: Terminal I/O control
When this command source is selected,
control commands are input through the DI
terminals of the AC drive. The DI terminal
control commands can be set according to
different scenarios, such as start/stop,
forward/reverse run, jog, two-wire/three-
wire control, multi-speed, and other
functions. It is suitable for most applications.
2: Communication control
When this command source is selected,
control commands are input through remote
communication. It is applicable to scenarios
requiring remote control or centralized
control of multiple devices.
4.1.1.2 Operating Panel Control
When F0-02 is set to 0, the operation commands for the AC drive are issued by pressing (RUN key)
and
(stop command/fault reset key) on the operating panel.
● Pressing (RUN key) on the operating panel enables the AC drive to run immediately (the RUN
indicator is ON).