Parameter Group
-210-
2 Parameter Group
2.1 F0: Basic Parameters
F0-00
G/P type
Address:
61440
Min.:
1
Unit:
-
Max.: 2 Data type: UInt16
Default: Model dependent Change: Unchangeable
Value Range:
1: G type (constant-torque load)
2: P type (fan and pump)
Description
1: G type (constant-torque load)
The G type models typically carry constant-torque loads with large overload capacity. The overload
capacity is 150% in general. Such loads include conveyor belts and cranes, for example.
2: P type (fan and pump)
F0-01
Motor 1 control mode
Address:
61441
Min.:
0
Unit:
-
Max.: 5 Data type: UInt16
Default:
2
Change:
At stop
Value Range:
0: SVC
1: Reserved
2: V/f control
3: Reserved
4: Reserved
5: VC++
Description
0: Sensorless vector control (SVC)
It is a type of open-loop vector control applicable to high-performance control applications, where
one AC drive can drive only one motor. It is used for loads such as machine tools, centrifuges, wire
drawing machines, and injection molding machines.
2: V/f control (open loop speed control)
It is applicable to applications with no high requirements on load control performance, such as fans
and pumps. The V/f control mode is the only choice if one AC drive needs to drive multiple motors.
5: PMVVC (synchronous motor speed open loop control)
It is suitable for loads with low precision requirements, such as fans and pumps.
F0-02
Command source
Address:
61442
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Operating panel of the power supply unit/LCD operating panel/Software tool
1: Terminal
2: Communication