Function Applications
-551-
4.9.4 Current Running Time Threshold
Para. No. Name
Default
Value Range Description
F8-58
Current running
time threshold
0.0 min 0.0 min to 6500.0 min
When the current running duration
reaches the value of F8-58, the DO
terminal outputs an active signal.
Only the current running duration
counts. The previous running
duration is not included.
F8-60
Deceleration time
for emergency stop
Model
dependent
0.0s to 6500.0s
F8-60 is added to define the
emergency stop deceleration time.
The AC drive decelerates according
to the set deceleration time when
the terminal emergency stop
function is triggered. When the
deceleration time is 0s in V/f mode,
the AC drive decelerates according
to the minimum unit time.