Function Applications
-437-
Step
Related
Parameters
Description
Step 5: Set the frequency
corresponding to each
speed reference.
FC-00 to FC-15
The frequency corresponding to each speed reference is set to a
percentage value. 100% corresponds to the maximum frequency
(F0-10).
F0-10
When multi-reference is used as the frequency reference source,
the value 100% of FC-00 to FC-15 corresponds to the maximum
frequency (F0-10).
The four multi-reference terminals provide 16 state combinations, corresponding to 16 reference
values, as listed in the following table.
Table 4–3 State combinations of the four multi-reference terminals
K4 K3 K2 K1
Reference
Parameter
OFF OFF OFF OFF
Multi-reference 0
FC-00
OFF OFF OFF ON
Multi-reference 1
FC-01
OFF OFF ON OFF
Multi-reference 2
FC-02
OFF OFF ON ON
Multi-reference 3
FC-03
OFF ON OFF OFF
Multi-reference 4
FC-04
OFF ON OFF ON
Multi-reference 5
FC-05
OFF ON ON OFF
Multi-reference 6
FC-06
OFF ON ON ON
Multi-reference 7
FC-07
ON OFF OFF OFF
Multi-reference 8
FC-08
ON OFF OFF ON
Multi-reference 9
FC-09
ON OFF ON OFF
Multi-reference 10
FC-10
ON OFF ON ON
Multi-reference 11
FC-11
ON ON OFF OFF
Multi-reference 12
FC-12
ON ON OFF ON
Multi-reference 13
FC-13
ON ON ON OFF
Multi-reference 14
FC-14
ON ON ON ON
Multi-reference 15
FC-15
4.1.2.6 Setting the Main Frequency Through Simple PLC
Step 1: Set F0-03 to 7 to select simple PLC as the main frequency reference.
Step 2: Set parameters FC-00...FC-15 and FC-18...FC-49 to define the running time and acceleration/
deceleration time for each reference.