Parameter Group
-354-
A1-09
AI3 function (used as DI)
Address:
41225
Min.:
0
Unit:
-
Max.: 63 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Same as F4-01
Description
Same as F4-01
A1-10
AI active mode (used as DI)
Address:
41226
Min.:
0
Unit:
-
Max.: 111 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Ones:
0: Active high
1: Active low
Tens:
0: Active high
1: Active low
Hundreds:
0: Active high
1: Active low
Description
Same as F4-01
2.19 A5: Control Optimization Parameters
A5-00
DPWM switchover frequency upper limit
Address:
42240
Min.:
0.00
Unit:
Hz
Max.: 50.00 Data type: UInt16
Default:
12.00
Change:
At once
Value Range:
0.00 Hz to 50.00 Hz
Description
The AC drive supports two PWM modes: CPWM and DPWM. When the running frequency is higher than
A5-00 (switchover frequency), the DPWM mode is used. When the running frequency is lower than
A5-00 (switchover frequency), the CPWM mode is used. The DPWM mode can improve the AC drive
efficiency, and the CPWM mode can reduce the motor noise.
Increasing the value of this parameter to the maximum frequency will reduce the motor noise.