Function Applications
-492-
Para. No. Function Default
Value Range Description
F2-13
Low-speed current loop Kp adjustment
1.0 0.1 to 10.0 
The value is obtained automatically
through motor auto-tuning.
F2-14
Low-speed current loop Ki adjustment
1.0 0.1 to 10.0 
F2-15
High-speed current loop Kp adjustment
1.0 0.1 to 10.0 
F2-16
High-speed current loop Ki adjustment
1.0 0.1 to 10.0 
4.4.10 Improving Performance of Field-Weakening Range
Para.
No.
Function Default
Value Range Description
F2-21
Maximum output voltage
coefficient
105% 100% to 110%
Indicates the boost capacity on the basis of maximum voltage of
the AC drive.
Increasing F2-21 improves the maximum loading capacity in
motor field-weakening range, but increases motor current ripple
and motor temperature. Decreasing F2-21 weakens the maximum
loading capacity in motor field-weakening range, but reduces
motor current ripple and motor temperature. Generally, this
parameter needs no adjustment.