Parameter Group
-266-
Min.:
0
Unit:
-
Max.: 11111 Data type: UInt16
Default:
0
Change:
At once
Value Range:
Ones:
0: Positive logic
1: Negative logic
Tens:
0: Positive logic
1: Negative logic
Hundreds:
0: Positive logic
1: Negative logic
Thousands:
0: Positive logic
1: Negative logic
Ten thousands:
0: Positive logic
1: Negative logic
Description
0: Positive logic (same as NO contact)
The DO/RO terminal is active when it is internally connected to the COM terminal.
The DO/RO terminal is inactive when it is disconnected from the COM terminal.
1: Negative logic (same as NC contact)
The DO/RO terminal is active when it is disconnected from the COM terminal.
The DO/RO terminal is inactive when it is internally connected to the COM terminal.
2.7 F6: Start/Stop Control
F6-00
Start Modes
Address:
62976
Min.:
0
Unit:
-
Max.:
2
Data type:
UInt16
Default:
0
Change:
At once
Value Range:
0: Direct start
1: Flying start (asynchronous motor)
2: Pre-excitation start (asynchronous motor)
Description
0: Direct start
This mode is applicable to most loads. Startup with the startup frequency is applicable to load
hoisting applications such as elevators and cranes.