Function Applications
-513-
Para. No. Name
Default
Value Range Description
F8-47
Timing duration
source
0
0: F8-48
1: AI1
2: AI2
When it is set to 0, the timing duration
is set by F8-48.
When it is set to 1, the timing duration
= (AI1 voltage/10 V) x F8-48. 100% of
analog input corresponds to the value
of F8-48.
When it is set to 2, the timing duration
= (AI2 voltage/10 V) x F8-48. 100% of
analog input corresponds to the value
of F8-48.
F8-48
Timing duration
0.0 min 0.0 min to 6500.0 min
The timing duration is defined by F8-
47 and F8-48.
4.5.4 AI1 Voltage Upper/Lower Limit
Para. No. Name
Default
Value Range Description
F8-49
AI1 input voltage lower
limit
3.10 V 0.00 V to F8-50
When the AI1 input voltage is higher
than F8-50 or lower than F8-49, the
DO terminal outputs an active signal
indicating "AI1 input limit exceeded".
F8-50
AI1 input voltage
upper limit
6.80 V F8-49 to 10.00 V
4.5.5 IGBT Temperature
Para. No. Name
Default
Value Range Description
F8-51
IGBT temperature
reach
75°C 0°C to 100°C
When the IGBT heatsink
temperature reaches the
value of F8-51, the DO/RO
terminal outputs an active
signal.
F7-07
Heatsink temperature
of IGBT
-
–20.0°C to +120.0°C
Heatsink temperature of
the IGBT