Function Applications
-510-
Related Parameters
Para. No. Name
Default
Value Range Description
F8-38
Zero current
detection level
5.0%
0.0% to 300.0%
(rated motor
current)
When the output
current of the AC
drive is lower than or
equal to F8-38 (zero
current detection
level) for longer than
the time defined by
F8-39 (zero current
detection delay), the
DO terminal outputs
an active signal.
F8-39
Zero current
detection delay
0.10s 0.00s to 600.00s
4.5.3.2 Output Overcurrent Threshold
When the output current of the AC drive is higher than F8-40 (output current threshold) for longer than
the time defined by F8-41 (output overcurrent detection delay), the DO terminal outputs an active
signal.
Figure 4-62 Output overcurrent threshold
Related Parameters
Para. No. Name
Default
Value Range Description
F8-40
Output
overcurrent
threshold
200.0%
0.0% (no detection)
0.1% to 300.0%
(rated motor
current)
When the output current of the AC drive is
higher than F8-40 (output current threshold)
for longer than the time defined by F8-41
(output overcurrent detection delay), the DO
terminal outputs an active signal.
F8-41
Output
overcurrent
detection
delay
0.00s 0.00s to 600.00s
4.5.3.3 Detection Level of Current
When the output current of the AC drive is within the range of (detection level of current±detection
width of current) x (rated motor current), the DO terminal outputs an active signal.