Software Tools
-413-
Table 3–4 Units
Unit Description
kWh
Energy unit
RPM
Speed unit
Hz
Frequency unit
A
Current unit
V
Voltage unit
°C Temperature unit
% Percentage
3.1.2 Related Parameters
Table 3–5 Parameters related to the operating panel
Para. No. Name
Default
Value Range Description
F7-01
MF.K key function
0
0: MF.K key disabled
1: Switchover between operating
panel control and remote
command control (terminal or
communication)
2: Switchover between forward and
reverse run
3: Forward jog
4: Reverse jog
The MF.K key is a multi-functional key. This parameter is
used to set the function of the MF.K key.
0: MF.K key disabled
The MF.K key does not work.
1: Switchover between operating panel control and
remote command control (terminal or communication)
When F0-02 is set to 0 (operating panel), the MF.K does
not work. When F0-02 is set to 1 (terminal), the MF.K key
implements switchover from terminal I/O control to
operating panel control. When F0-02 is set to 2
(communication), the MF.K key implements switchover
from communication control to operating panel control.
2: Switchover between forward and reverse run
The direction of the frequency reference can be changed
by using the MF.K key. This function is valid only when the
command source is set to operating panel control.
3: Forward jog
Forward jog (FJOG) can be enabled by using the MF.K key.
This function is valid only when the command source is
set to operating panel control.
4: Reverse jog
Reverse jog (RJOG) can be enabled by using the MF.K key.
This function is valid only when the command source is
set to operating panel control.
F7-02
STOP key function
0
0: Valid only under operating panel
control
1: Valid in all operation modes
The STOP key on the operating panel is used for stop/
reset. This parameter is used to set the function of this
key.
0: Valid only under operating panel control
This key is valid only under operating panel control.
1: Valid in all operation modes
This key is valid in all operation modes.