Parameter Group
-337-
3: AI3
The frequency reference 0 is set by AI3 input.
5: PID
The frequency reference 0 is set by PID.
6: Preset frequency (F0-08)
The frequency reference 0 is set by F0-08 (preset frequency).
2.14 FD: Communication Parameters
FD-02
Local address
Address:
64770
Min.:
0
Unit:
-
Max.: 247 Data type: UInt16
Default:
1
Change: Unchangeable
Value Range:
0 to 247
Description
When the local address is set to 0 (broadcast address), host controller broadcast is enabled.
The local address must be unique in the range of 1 to 247, which is the basis for point-point
communication between the AC drive and host controller.
FD-06
Communication fault reset
Address:
64774
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
1
Change:
At stop
Value Range:
0 to 1
Description
This parameter defines whether to reset the communication fault automatically.
FD-08
Last allocated station number
Address:
64776
Min.:
0
Unit:
-
Max.: 65535 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0 to 65535
Description
When the station number allocation is normal, this value is the station number allocated this time.
When the station number allocation is abnormal, the current value is used as the current station
number.
FD-09
CANopen/CANlink communication state
Address:
64777
Min.:
0
Unit:
-
Max.: 999 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range: