Parameter Group
-336-
Description
FC-18 to FC-49 define the operation time and acceleration/deceleration time of each of the 16 multi-
speed references respectively. The operation duration of each reference is the sum of the acceleration
or deceleration time plus the time of operation at constant speed and target frequency.
FC-49
Acceleration/Deceleration time of PLC reference 15
Address:
64561
Min.:
0
Unit:
-
Max.: 3 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0 to 3
Description
FC-18 to FC-49 define the operation time and acceleration/deceleration time of each of the 16 multi-
speed references respectively. The operation duration of each reference is the sum of the acceleration
or deceleration time plus the time of operation at constant speed and target frequency.
FC-50
PLC running time unit
Address:
64562
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: s (second)
1: h (hour)
Description
This parameter defines the unit of the PLC operation time.
FC-51
Multi-reference 0 source
Address:
64563
Min.:
0
Unit:
-
Max.: 6 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: FC-00
1: AI1
2: AI2
3: AI3
4: Reserved
5: PID
6: Preset frequency (F0-08) (which can be modified by terminal UP/DOWN)
Description
Reference 0 can be set by digital setting, analog input, PID, and preset frequency.
0: FC-00
The frequency reference 0 is set by FC-00.
1: AI1
The frequency reference 0 is set by AI1 input.
2: AI2
The frequency reference 0 is set by AI2 input.