Function Applications
-466-
Para. No.
Display Description
F5-00
D0/RO1 of the drive unit maps to DIO1 of the power supply unit.
F5-02
D0/RO2 of the drive unit maps to relay RO1 of the power supply
unit.
Table 4–18 Related parameters
Para. No. Name
Default
Value Range Description
F5-00
DO1/RO1 hardware
source
0
0: None
1: DIO1 of the power supply unit
2: DIO2 of the power supply unit
3: DIO3 of the power supply unit
4: DIO4 of the power supply unit
5: RO1 of the power supply unit
101: DO1/RO1 of extension card 1
102: DO2/RO2 of extension card 1
103: DO3/RO3 of extension card 1
104: DO4/RO4 of extension card 1
105: DO5/RO5 of extension card 1
106: DO6/RO6 of extension card 1
107: DO7/RO7 of extension card 1
108: DO8/RO8 of extension card 1
201: DO1/RO1 of extension card 2
202: DO2/RO2 of extension card 2
203: DO3/RO3 of extension card 2
204: DO4/RO4 of extension card 2
205: DO5/RO5 of extension card 2
206: DO6/RO6 of extension card 2
207: DO7/RO7 of extension card 2
208: DO8/RO8 of extension card 2
This parameter
defines the
hardware source of
the output
terminal.
F5-02
DO2/RO2 hardware
source
0
F5-04
DO3/RO3 hardware
source
0
F5-06
DO4/RO4 hardware
source
0
F5-08
DO5/RO5 hardware
source
0
The value range of the parameters in the preceding table changes automatically. For details, see
4.3.1.1 Sources of DI Terminals
on page 458
.
4.3.2.2 Functions of DO Terminals
The AC drive is equipped with 5 multi-function digital output terminals. F5-01 to F5-09 define the
functions of the DO/RO terminals to indicate various working states and alarms of the AC drive. There
are a total of about 40 functions available to fulfill specific automatic control requirements.