Software Tools
-414-
Para. No. Name
Default
Value Range Description
F7-03
LED display 1 in
running state
31
Bit00: Running frequency (Hz)
Bit01: Frequency reference (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI state
Bit08: DO state
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: AI3 voltage (V)
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID reference
To display a parameter during running, set the
corresponding bit to 1, convert the binary number to a
hexadecimal equivalent, and set it in F7-03.
F7-04
LED display 2 in
running state
0
Bit00: PID feedback
Bit01: PLC stage
Bit02: Reserved
Bit03: Running frequency 2 (Hz)
Bit04: Remaining running time
Bit05: Reserved
Bit06: Reserved
Bit07: Reserved
Bit08: Linear speed
Bit09: Current power-on time (min)
Bit10: Current running time (min)
Bit11: Reserved
Bit12: Communication
Bit13: Reserved
Bit14: Main frequency X display
Bit15: Auxiliary frequency Y display
To display a parameter during running, set the
corresponding bit to 1, convert the binary number to a
hexadecimal equivalent, and set it in F7-04.