Software Tools
-415-
Para. No. Name
Default
Value Range Description
F7-05
LED display in stop
state
51
Bit00: Frequency reference (Hz)
Bit01: Bus voltage (V)
BIT02: DI state
BIT03: DO state
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: AI3 voltage (V)
Bit07: Count value
Bit08: Length value
Bit09: PLC stage
Bit10: Load speed display
Bit11: PID reference
Bit12: Reserved
To display a parameter upon stop, set the corresponding
bit to 1, convert the binary number to a hexadecimal
equivalent, and set it in F7-05.
FP-01
Parameter
initialization
1
0: No operation
1: Restore factory defaults mode 1
2: Clear records
4: Back up current parameters
501: Restore user backup
parameters
This parameter is used to set the corresponding action
upon parameter initialization of the AC drive.
0: No operation
The AC drive does not perform any operation.
1: Restore factory defaults mode 1
Most of the parameters are restored to factory defaults.
However, motor parameters including F0-10 (maximum
frequency), F0-22 (decimal places of frequency reference),
fault records, F7-09 (accumulative running time), F7-12
(accumulative power-on time), F7-13 (accumulative
power generation), and F7-14 (accumulative power
consumption) are not restored.
2: Clear records
The fault records, F7-09 (accumulative running time), F7-
12 (accumulative power-on time), F7-13 (accumulative
power generation), and F7-14 (accumulative power
consumption) are cleared.
4: Back up current parameters
The current parameter setting is backed up.
501: Restore user backup parameters
Parameters backed up by setting FP-01 to 4 are restored.