Parameter Group
-353-
Three ways of setting VDI status are available and can be selected by using A1-05.
When this parameter is set to 0, the VDI state is determined by the binary bit of A1-06.
When it is set to 1, the VDI state is determined by the state (active or inactive) of the corresponding
DO/RO. VDIx is uniquely bound to DOx/ROx (x ranges from 1 to 5).
When it is set to 2, the VDI state is determined by the state (active or inactive) of the corresponding DI.
VDIx is uniquely bound to DIx (x ranges from 1 to 5).
A1-06 VDI state
Address:
41222
Min.:
0
Unit:
-
Max.: 11111 Data type: UInt16
Default:
0
Change:
At once
Value Range:
Ones:
0: Inactive
1: Active
Tens:
0: Inactive
1: Active
Hundreds:
0: Inactive
1: Active
Thousands:
0: Inactive
1: Active
Ten thousands:
0: Inactive
1: Active
Description
This parameter defines whether VDIx (x ranges from 1 to 5) is active or inactive.
A1-07
AI1 function (used as DI)
Address:
41223
Min.:
0
Unit:
-
Max.: 63 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Same as F4-01
Description
Same as F4-01
A1-08
AI2 function (used as DI)
Address:
41224
Min.:
0
Unit:
-
Max.: 63 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Same as F4-01
Description
Same as F4-01