Parameter Group
-260-
0: Not selected
1: Power supply unit - DIO1
2: Power supply unit - DIO2
3: Power supply unit - DIO3
4: Power supply unit - DIO4
5: Power supply unit - RO1
101: Extension card 1 - DO1/RO1
102: Extension card 1 - DO2/RO2
103: Extension card 1 - DO3/RO3
104: Extension card 1 - DO4/RO4
105: Extension card 1 - DO5/RO5
106: Extension card 1 - DO6/RO6
107: Extension card 1 - DO7/RO7
108: Extension card 1 - DO8/RO8
201: Extension card 2 - DO1/RO1
202: Extension card 2 - DO2/RO2
203: Extension card 2 - DO3/RO3
204: Extension card 2 - DO4/RO4
205: Extension card 2 - DO5/RO5
206: Extension card 2 - DO6/RO6
207: Extension card 2 - DO7/RO7
208: Extension card 2 - DO8/RO8
Description
This parameter defines the hardware source of the output terminal.
F5-01
DO1/RO1 function
Address:
62721
Min.:
0
Unit:
-
Max.: 50 Data type: UInt16
Default:
3
Change:
At once
Value Range:
0 to 50
Description
This parameter defines the function of the output terminal.
0: No output
The output terminal has no function.
1: AC drive in running
The terminal outputs an "active" signal when the AC drive is running with output frequency (which
can be 0).
2: Ready to run
The terminal outputs an "active" signal when the AC drive is ready for running without any fault after
power-on.
3: Fault output 1 (stop upon fault)
When the AC drive coasts to stop or decelerates to stop upon a fault, the DO terminal outputs an
"active" signal after the AC drive stops completely.
4: Fault output 2
When the AC drive coasts to stop or decelerates to stop upon a fault (undervoltage excluded), the DO
terminal outputs an "active" signal after the AC drive stops completely.