Parameter Group
-349-
Max.: 2.000 Data type: Int16
Default:
1.000
Change:
At once
Value Range:
-2.000% to 2.000%
Description
This parameter defines digital setting of the torque in torque control mode. The torque reference is a
relative value. The value 100.0% corresponds to the rated torque of the AC drive. (The output torque
of the AC drive can be viewed by using U0-07, where the value 100% corresponds to the rated torque
of the AC drive. The output torque of the motor can be viewed by using U0-06, where the value 100%
corresponds to the rated torque of the motor.) The value range is –200.0% to +200.0%, indicating that
the maximum torque is twice the rated torque.
When the torque reference is a positive value, the AC drive runs in the forward direction. When it is a
negative value, the AC drive runs in the reverse direction.
A0-04
Torque filter time
Address:
40964
Min.:
0.000
Unit:
s
Max.: 5.000 Data type: UInt16
Default:
0.000
Change:
At once
Value Range:
0.000s to 5.000s
Description
This parameter defines the torque filter time. It can be adjusted based on the torque source.
A0-05
Speed limit digital setting
Address:
40965
Min.:
-120.0
Unit:
%
Max.: 120.0 Data type: Int16
Default:
0.0
Change:
At once
Value Range:
-120.0% to 120.0%
Description
This parameter defines the digital setting of the speed limit.
A0-07
Acceleration time (torque)
Address:
40967
Min.:
0.00
Unit:
s
Max.: 650.00 Data type: UInt16
Default:
1.00
Change:
At once
Value Range:
0.00s to 650.00s
Description
This parameter defines the torque reference acceleration time.
A0-08
Deceleration time (torque)
Address:
40968
Min.:
0.00
Unit:
s
Max.: 650.00 Data type: UInt16
Default:
1.00
Change:
At once
Value Range:
0.00s to 650.00s