Parameter Group
-350-
Description
This parameter defines the torque reference deceleration time.
A0-09
Speed limit reference source
Address:
40969
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: A0-05
1: Frequency source
Description
This parameter defines the speed limit reference source. When it is set to 0, A0-05 is used as the
source. When it is set to 1, the frequency source is used as the source.
A0-10
Speed limit offset
Address:
40970
Min.:
0.00
Unit:
-
Max.: 655.35 Data type: UInt16
Default:
5.00
Change:
At once
Value Range:
0.00 to 655.35
Description
The parameter defines the speed limit offset. If the actual speed exceeds the limit by a value greater
than the speed limit offset, the output torque will be limited.
A0-11
Effective mode of speed limit offset
Address:
40971
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Bidirectional offset effective
1: Unidirectional offset effective
Description
When it is set to 0, bidirectional offset is effective. When it is set to 1, unidirectional offset is effective.
A0-12
Acceleration time (frequency)
Address:
40972
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
1.0
Change:
At once
Value Range:
0.0s to 6500.0s
Description
This parameter defines the frequency acceleration time, which is valid in torque control mode.
A0-13
Deceleration time (frequency)
Address:
40973
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
1.0
Change:
At once