Parameter Group
-315-
Default:
50.0
Change:
At once
Value Range:
0.0% to 100.0%
Description
When FA-00 (PID reference source) is set to 0, this parameter must be set. The setpoint 100%
corresponds to the maximum feedback value.
FA-02
PID feedback source
Address:
64002
Min.:
0
Unit:
-
Max.: 8 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: AI1
1: AI2
2: AI3
3: AI1 to AI2
4: Reserved
5: Communication
6: AI1 + AI2
7: Max. (|AI1|, |AI2|)
8: Min. (|AI1|, |AI2|)
Description
This parameter defines the PID feedback source.
FA-03
PID action direction
Address:
64003
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Forward
1: Reverse
Description
0: Forward
When the feedback value is lower than the PID reference, the output frequency of the AC drive
increases.
1: Reverse
When the feedback value is lower than the PID reference, the output frequency of the AC drive
decreases.
FA-04
PID reference and feedback range
Address:
64004
Min.:
0
Unit:
-
Max.: 65535 Data type: UInt16
Default:
1000
Change:
At once
Value Range:
0 to 65535