Parameter Group
-84-
2: Clear records
Clear record information. Clear fault records and accumulative running time of the power supply unit.
4: Back up the current user parameters
Back up the current parameter settings. The current parameter settings are backed up to facilitate
restoration after parameter adjustment.
501: Restore user backup parameters
Restore your previously backed-up parameters, that is, restore parameters that are backed up by
setting FP-01 to 4.
FP-03
Monitoring parameter display
Address:
7939
Min.:
0
Unit:
-
Max.: 127 Data type: UInt16
Default:
251
Change:
At once
Value Range:
Bit00: Bus voltage
Bit01: Heatsink temperature
Bit02: Ambient temperature
Bit03: Usr line voltage
Bit04: Ust line voltage
Bit05: Utr line voltage
Bit06: Three-phase imbalance factor
Description
This parameter defines the monitoring state of parameters switched by pressing the > key under the
level 0 menu of the operating panel.
FP-05
I/O card parameter restoration
Address:
7941
Min.:
0
Unit:
-
Max.: 255 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Invalid
1: Extension I/O1
2: Extension I/O2
3: Extension I/O3
255: All extension I/Os
Description
This parameter defines whether to restore the extension card with AI input to factory defaults. All AI
calibration can be set by using parameters in group AC. After parameters in group AC are set on site,
you can set FP-05 to restore factory defaults if required.
FP-06
Local parameter backup mode
Address:
7942
Min.:
1
Unit:
-
Max.: 2 Data type: UInt16
Default:
1
Change:
At once
Value Range:
1: Back up all parameters
2: Back up non-motor parameters