EasyManua.ls Logo

Inovance MD800 Series - Page 220

Inovance MD800 Series
565 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Group
-219-
0: Non-retentive
F0-08 (preset frequency) set through the operating panel and frequency modifications made by using
the and keys or UP and DOWN of terminals are cleared when the AC drive stops.
1: Retentive
F0-08 (preset frequency) set through the operating panel and frequency modifications made by using
the and keys or UP and DOWN of terminals are retained when the AC drive stops.
F0-25
Acceleration/Deceleration time base frequency
Address:
61465
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Maximum frequency (F0-10)
1: Frequency reference
2: 100 Hz
Description
This parameter defines the target frequency during acceleration and the starting frequency during
deceleration.
F0-26
Base frequency for UP/DOWN modification during running
Address:
61466
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Running frequency
1: Frequency reference
Description
This parameter defines the base frequency from which the target frequency is adjusted by using the
UP/DOWN key of the operating panel during operation.
If it is set to 0 and the running frequency is 25 Hz, the target frequency will change from 25 Hz at a
certain rate when the UP key is pressed.
If it is set to 1, the target frequency will change from the original target frequency when the UP key is
pressed.
F0-27
Main frequency coefficient
Address:
61467
Min.:
0.00
Unit:
%
Max.: 100.00 Data type: UInt16
Default:
10.00
Change:
At once
Value Range:
0.00% to 100.00%
Description
This parameter defines the main frequency reference coefficient when the frequency superposition
mode is Main x Auxiliary. The value 100.00% corresponds to the target main frequency reference.
F0-28
Auxiliary frequency coefficient
Address:
61468
Min.:
0.00
Unit:
%
Max.: 100.00 Data type: UInt16

Table of Contents

Other manuals for Inovance MD800 Series

Related product manuals