Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F2-32 61984
Expected speed loop
bandwidth (low speed)
1.0 Hz to 200.0 Hz 10.0 Hz At once
“
F2-32
”
on page
234
F2-33 61985
Expected speed loop
bandwidth (zero speed)
1.0 Hz to 200.0 Hz 10.0 Hz At once
“
F2-33
”
on page
234
F2-34 61986
Expected speed loop
damping ratio:
(unchanged generally)
0.100 to 65.000 1.000 - At once
“
F2-34
”
on page
234
F2-52 62004
Decoupling control
0: Disabled
1: Enabled
0 -
At stop
“
F2-52
”
on page
234
F2-53 62005
Power limit during
generating
0: Disabled
1: Enabled
0 -
At stop
“
F2-53
”
on page
234
F2-54 62006
Power limit during
generating
0.0% to 200.0% 0.0 %
At stop
“
F2-54
”
on page
235
F2-55 62007
Flux closed loop mode
0 to 1111 1010 -
At stop
“
F2-55
”
on page
235
F2-56 62008
AC drive output current
upper limit
0.0% to 170.0% 150.0 %
At stop
“
F2-56
”
on page
235
F3-00 62208
V/f curve reference
0: Straight-line V/f curve
1: Multi-point V/f curve
2: Square V/f curve
3: 1.2-power V/f curve
4: 1.4-power V/f curve
6: 1.6-power V/f curve
8: 1.8-power V/f curve
10: V/f complete separation mode
11:V/f half separation mode
0 -
At stop
“
F3-00
”
on page
235
F3-01 62209
Torque boost
0.0% to 30.0%
Model
dependent
% At once
“
F3-01
”
on page
237
F3-02 62210
Cutoff frequency of
torque boost
0.00 Hz to 655.35 Hz 50.00 Hz
At stop
“
F3-02
”
on page
237
F3-03 62211
Multi-point V/f frequency
1
0.00 Hz to 655.35 Hz 0.00 Hz
At stop
“
F3-03
”
on page
237
F3-04 62212
Multi-point V/f voltage 1
0.0% to 100.0% 0.0 %
At stop
“
F3-04
”
on page
237
List of Drive Unit Parameters
-146-