Parameter Group
-213-
0: Digital setting (preset frequency (F0-08) that can be changed by pressing UP/DOWN, non-retentive
upon power failure)
1: Digital setting (preset frequency (F0-08) that can be changed by pressing UP/DOWN, retentive at
power failure)
2: AI1
3: AI2
4: AI3
5: Reserved
6: Multi-reference
7: Simple PLC
8: PID
9: Communication
10: Reserved
Description
Same as F0-03
F0-05
Base value of range of auxiliary frequency source Y for superposition
Address:
61445
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Relative to maximum frequency
1: Relative to main frequency X
Description
0: Relative to maximum frequency
The auxiliary frequency at superposition is equal to the auxiliary frequency source range (F0-06)
multiplied by the maximum frequency (F0-10).
1: Relative to main frequency X
The auxiliary frequency at superposition is equal to the auxiliary frequency source range (F0-06)
multiplied by the main frequency X.
F0-06
Range of auxiliary frequency source Y for superposition
Address:
61446
Min.:
0
Unit:
%
Max.: 150 Data type: UInt16
Default:
100
Change:
At once
Value Range:
0% to 150%
Description
0: Relative to maximum frequency
The auxiliary frequency at superposition is equal to the auxiliary frequency source range (F0-06)
multiplied by the maximum frequency (F0-10).
1: Relative to main frequency X
The auxiliary frequency at superposition is equal to the auxiliary frequency source range (F0-06)
multiplied by the main frequency X.
F0-07
Frequency source superposition
Address:
61447