Parameter Group
-256-
Default:
0.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of the minimum input point on AI curve 1, that is, the percentage of
the minimum analog input relative to the maximum frequency.
F4-33
AI curve 1 maximum input
Address:
62497
Min.:
–10.00
Unit:
V
Max.: 10.00 Data type: Int16
Default:
10.00
Change:
At once
Value Range:
–10.00 V to 10.00 V
Description
This parameter defines the x-axis of the maximum input point on AI curve 1, that is, the maximum
analog input voltage (or maximum analog input current).
F4-34
Percentage corresponding to AI curve 1 maximum input
Address:
62498
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
100.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of the maximum input point on AI curve 1, that is, the percentage of
the maximum analog input relative to the maximum frequency.
F4-35
AI curve 2 minimum input
Address:
62499
Min.:
–10.00
Unit:
V
Max.: 10.00 Data type: Int16
Default:
0.00
Change:
At once
Value Range:
–10.00 V to 10.00 V
Description
This parameter defines the x-axis of the minimum input point on AI curve 2, that is, the minimum
analog input voltage (or minimum analog input current).
F4-36
Percentage corresponding to AI curve 2 minimum input
Address:
62500
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
0.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of the minimum input point on AI curve 2, that is, the percentage of
the minimum analog input relative to the maximum frequency.