Parameter Group
-263-
34: AI1 input limit exceeded
The terminal outputs an "active" signal when the AI1 input is higher than the value of F8-49 (AI1 input
voltage upper limit) or lower than the value of F8-50 (AI1 input voltage lower limit).
35: AI1 > AI2
The terminal outputs an "active" signal when the AI1 input is higher than the AI2 input.
36: PLC cycle completed
The terminal outputs a pulse signal with the width of 250 ms when the simple PLC completes one
cycle.
37: Communication control
Whether the terminal is active or inactive is determined by the setpoint in communication address
0x2001.
38: STO-EDM
The DO terminal outputs an "active" signal when STO is triggered.
40: Running at zero speed (no output at stop)
The terminal outputs an "active" signal when the output frequency of the AC drive is 0 during running.
When the AC drive stops, an "inactive" signal is output.
41: Running at zero speed 2 (output at stop)
The terminal outputs an "active" signal when the output frequency of the AC drive is 0 during running.
When the AC drive stops, the "active" signal is retained.
43: Reverse running
The terminal outputs an "active" signal when the AC drive runs in the reverse direction.
44 to 50: Reserved
F5-02
DO2/RO2 hardware source
Address:
62722
Min.:
0
Unit:
-
Max.: 208 Data type: UInt16
Default:
0
Change:
At once
Value Range:
Same as F5-00
Description
Same as F5-00
F5-03
DO2/RO2 function
Address:
62723
Min.:
0
Unit:
-
Max.: 50 Data type: UInt16
Default:
15
Change:
At once
Value Range:
Same as F5-01
Description
Same as F5-01
F5-04
DO3/RO3 hardware source
Address:
62724
Min.:
0
Unit:
-
Max.:
208
Data type:
UInt16
Default:
0
Change:
At once
Value Range:
Same as F5-00