Parameter Group
-327-
Max.: 100.0 Data type: Int16
Default:
0.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
Same as FC-00
FC-15
Multi-reference 15
Address:
64527
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
0.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
Same as FC-00
FC-16
Simple PLC running mode
Address:
64528
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Stop after running for one cycle
1: Keep final values after running for one cycle
2: Repeat after running for one cycle
Description
When the simple PLC is used as the main frequency source, FC-16 defines the running mode of the
simple PLC, and FC-17 defines whether the operation stage and running frequency of the PLC before
power failure are retentive upon power failure or shutdown.
0: Stop after running for one cycle
The AC drive stops automatically after running for one cycle and starts again only after receiving a
running command.
1: Keep the final value after running for one cycle
The AC drive keeps the final running frequency and direction after running for one cycle and starts
from the initial PLC state upon restart.
2: Repeat after running for one cycle
The AC drive automatically starts another cycle after running for one cycle and stops only after
receiving a stop command.
FC-17
Simple PLC memory retention
Address:
64529
Min.:
0
Unit:
-
Max.: 11 Data type:
UInt16
Default:
0
Change:
At once
Value Range: