Parameter Group
-38-
F1-04
Braking transistor short-circuit
Address:
61700
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
1
Change:
At once
Value Range:
0: Disabled
1: Enabled
Description
When the braking transistor short circuit detection function is enabled, the system will report E61.01
or E61.03 if the braking transistor is short-circuited.
F1-05
Input phase loss fault
Address:
61701
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
2
Change:
At once
Value Range:
0: Disabled
1: Enabled
2: Warning
Description
This parameter defines the action upon an input phase loss fault.
This parameter is applicable only to three-phase 380 V input models, but not single-phase 220 V
models.
When it is set to 0, no alarm is generated when input phase loss occurs.
When it is set to 1, E12.01 is reported when input phase loss occurs.
When it is set to 2, A12.01 is reported as a warning when input phase loss occurs.
F1-06
Input overvoltage fault
Address:
61702
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
2
Change:
At once
Value Range:
0: Disabled
1: Enabled
2: Warning
Description
This parameter defines the action upon an input overvoltage fault.
This parameter specifies whether to generate an alarm upon an input overvoltage fault.
When it is set to 0, no alarm is generated.
When it is set to 1, E12.04 is reported when input overvoltage occurs.
When it is set to 2, A12.04 is reported when input overvoltage occurs.
For three-phase 380 V models, the input overvoltage threshold is 576 V. For single-phase 220 V
models, the input overvoltage threshold is 288 V.
F1-07
Fan fault
Address:
61703
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16