Software Tools
-421-
Table 3–6 Motor parameters
Para. No. Name
Default
Value Range Description Setpoint
F1-00
Motor type
selection
0
0: Common
asynchronous
motor
1: Variable
frequency
asynchronous
motor
2: Synchronous
motor
A variable frequency motor can adjust its frequency and
speed according to the load. Where the voltage is low, it can
reduce the frequency and start reliably. Where the load is
light, it can reduce the frequency, speed, and current to save
electric energy.
A common asynchronous motor is suitable for applications
with normal voltage but often full load. It is designed based
on constant frequency and constant voltage. Therefore, it
may not meet all the frequency and speed control
requirements.
0
F1-01
Rated motor
power
Model
dependent
0.1 kW to 1000.0
kW
Rated motor power indicates the axis output power of the
motor working in rated conditions. Select a motor of proper
power rating based on the requirements of the mechanical
load, with due consideration to factors such as motor
heating, overload capacity, and starting capacity.
3.7 kW
F1-02
Rated motor
voltage
Model
dependent
1 V to 2000 V
Rated motor voltage indicates the voltage of the motor
during normal operation, which usually refers to the line
voltage.
380.0 V
F1-03
Rated motor
current
Model
dependent
0.1 A to 6553.5 A
Rated motor current indicates the current of the motor
during normal operation, which usually refers to the line
current.
9.0 A
F1-04
Rated motor
frequency
Model
dependent
0.01 Hz to 600.00
Hz
Rated motor frequency indicates the frequency of the power
supply connected to the stator winding under the rated
operation state of the motor.
50.00 Hz
F1-05
Rated motor
speed
Model
dependent
1 RPM to 65535
RPM
Rated motor speed indicates the speed of the rotor under the
rated operating state, and the unit is RPM.
1460 rpm
7. Set F1-37 to 2, and press ENTER. The operating panel displays
. Press the RUN key on
the operating panel for more than 3 seconds to start motor auto-tuning. During this process, the
RUN indicator is steady on, the TC indicator flashes, and the AC drive energizes the motor. After
about 1 minute, the panel displays 50.00, indicating that auto-tuning is completed.
8. Set F7-01 to 3, and then press to start forward jog of the motor.