Function Applications
-475-
Figure 4-33 Relationship between AI input voltages and DI states
Table 4–26 Related parameters
Para. No. Name
Default
Value Range Description
A1-07
Function selection for AI1
used as DI
0 0 to 60
Function setting of the AI used as DI is
the same as that of DIs. Functions 0 to
60 are set in the same way as normal
DIs.
A1-08
Function selection for AI2
used as DI
0 0 to 60
A1-09
Function selection for AI3
used as DI
0 0 to 60
A1-10
AI active mode (used as DI)
000
0: Active high
1: Active low
Ones: AI1
Tens: AI2
Hundreds: AI3
If the AI terminal is active high, it is
active when the corresponding bit of
A1-10 is set to 0 and inactive when
that bit of A1-10 is set to 1.
If the AI terminal is active low, it is
inactive when the corresponding bit of
A1-10 is set to 0 and active when that
bit of A1-10 is set to 1.