Function Applications
-501-
Figure 4-54 Schematic diagram of jog running
Related Parameters
Para. No. Name
Default
Value Range Description
F0-02
Operation command
source
0
0: Operating panel control
1: Terminal I/O control
2: Communication control
-
F0-25
Acceleration/
Deceleration time base
frequency
1
0: Maximum frequency (F0-10)
1: Target frequency
2: 100 Hz
-
F7-01
MF.K key function
0
0: MF.K key disabled
1: Switchover between operating panel
control and remote control (terminal I/O
control or communication control)
2: Switchover between forward and
reverse run
3: Forward jog
4: Reverse jog
-
F8-00
Jog frequency
2.00 Hz
0 to maximum frequency (F0-10)
-
F8-01
Jog acceleration time
20.0s 0.0s to 6500.0s
-
F8-02
Jog deceleration time
20.0s 0.0s to 6500.0s
-
F8-14
Reverse running
0
0: Reverse running allowed
1: Reverse running inhibited
-
F8-37
Jog preferred
0
0: Disabled
1: Enabled
-
Application
The following introduces how to set parameters related to jog running by taking implementation of jog
running using the operating panel as an example.