EasyManua.ls Logo

Insightec Exablate 2100V1 - Page 157

Default Icon
164 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WATER SYSTEM MAINTENANCE
Manual Part Number
157
condensation, circulate water in warming
state for ~5 min.
3.
High pressure
The water pressure in the
balloon is too high.
Drain 30 CC from the balloon, and more if the
error persists (up to reference volume).
4.
Low pressure
The water pressure in the
balloon is too low.
Fill 30 CC into the balloon, and more if the
error persists.
5.
High flow XD
The flow rate of the
circulating water is above
threshold.
Check visually for bubbles in the
balloon/hoses, the error might occur as
long as there are bubbles in the system.
If it occurs during transducer preparation
ignore it by pressing <Mute> on remote
control.
Check for water leaks.
6.
Low flow XD
The flow rate of the
circulating water is below
threshold.
Check visually for bubbles in the
balloon/hoses, the error might occur as
long as there are bubbles in the system.
If it occurs during transducer preparation
ignore it by pressing <Mute> on remote
control.
Check for water leaks.
Check water filter on the table.
Check for bend/ pinched hoses.
7.
Combined error
General error, as a result of
several errors at once.
Click “Reset” on the control panel.
8.
Chiller low/high
temp
The water temperature of
the chiller is not within
boundaries.
Check temperature reading on chiller
display (in equipment room).
9.
Chiller low level
The system diagnosed that
there is coolant level drop
inside the chiller coolant tank
(in equipment room).
Check for coolant leaks around the table
and along the hoses up to the chiller (in
equipment room).
Coolant may evaporate. Add coolant to
the chiller according to the level signs (in
equipment room).

Table of Contents