7.1.2. Electrical installation and safety inspection
CAUTION
Make sure that the electrical safety tests have been done according to local laws
and regulations.
CAUTION
If you remove touch protection for the inspection, install it back again.
NOTE
Note the name, number and revision of the electrical design documentation.
The electrical contractor does the electrical installation and safety
inspection. Its purpose is to verify that the installation obeys the local laws,
regulations, and requirements.
Item to inspect
Power Units
Station Charger
Satellite
Satellite Version 2
Liquid Cooled Satellite
Control Unit
AC Satellite
AC Satellite
with charging cables
Phase order of AC supply power cable
connections correct
• • • •
Tightening torques of AC supply power
cable connections correct
• • • •
DC output power cables correctly
labeled at both ends
• • • • • •
Tightening torques of DC output power
cable connections correct
• • • • • •
Control cables correctly labeled at
both ends
• • • • • •
Charging cable wires connected to
correct terminals
• • • • • • •
Cable bushings of charging cables
correctly tightened
• • • • • • •
Ethernet cables tested with LAN tester • • • • • • • •
CHARGING EQUIPMENT FOR ELECTRIC VEHICLES INSTALLATION MANUAL
CONFIDENTIAL – CERTIFIED PARTNERS 116 REV 2.40 EN 04-2024