NOTICE
Do not exceed the bending radius of the cable given by the cable manufacturer.
NOTE
AC Satellite is not connected to a charging power unit. It is connected directly to the
main power supply.
NOTE
Product datasheets are available at mediabank.kempower.com.
As the requirements of individual installations vary significantly, it is not
possible to give detailed instructions that are valid for all sites. Take into
account the local rules and requirements on electrical installations, cable
routing, and cable dimensioning. For assistance, contact Kempower Sales
Support.
The Kempower delivery includes the charging equipment and cabling
inside the units. Cabling from the AC main power supply to the unit(s),
cabling between the units, and any other components are the customer's
responsibility.
4.2.1. AC mains power cables to the charging power unit
NOTICE
Selecting the correct cable type and size is the electrical designer's responsibility.
Obey the relevant standards, local laws, and regulations. Take into account the
specific requirements of the installation site.
NOTE
The maximum wire size of the terminal is 2 x 240 mm
2
.
The neutral wire is not used in the Power Unit (TN-C network). If the network
cable has a neutral wire, it is connected to the cabinet's neutral wire
terminal block (N) to keep the wire securely in place. The neutral wire is not
connected to earth in the cabinet.
The neutral wire is only used in the Station Charger if it has an optional
AC charging output (TN-C-S network). The neutral wire is connected to the
cabinet's neutral wire terminal block (N).
Phases 1–3 (L1, L2, L3) and neutral (N) can be aluminum or copper wires. We
recommend using copper wire for protective earth (PE).
CHARGING EQUIPMENT FOR ELECTRIC VEHICLES INSTALLATION MANUAL
CONFIDENTIAL – CERTIFIED PARTNERS 37 REV 2.40 EN 04-2024