• DC auxiliary power wire for the user interface of the Satellite (+24 V)
•
If the distance between the charging power unit and the charging
point is more than 50 m, use two parallel auxiliary power wires to
compensate for voltage drop.
• Ground the cable shield at the charging power unit end.
• Ground wire (0 V)
See also
10: Examples of connecting output and control cables to charging
points and 11: Examples of connecting cables to the Satellites.
5.2.11. Installing the communication cables
NOTICE
Do not make holes or openings in the cabinet structure for the cables. Do not
route the cables through the connectors or cooling outlets behind the modules.
Changes or modifications, unless specifically agreed upon with Kempower, will void
the warranty.
NOTE
Each Satellite must have its own communication cable.
NOTE
Ground the Ethernet shield at one end only, either at the charging point or near
the Ethernet switch of the charging power unit.
Included in the delivery (inside
the Satellite)
Not included in the delivery
• Clip-type Ethernet terminal blocks
for the charging power unit and the
charging point
•
RJ45 connectors
• Extension Ethernet cable between
the Ethernet terminal block and
the Ethernet switch in the control
module
• Ethernet SuperCAT 6 cable,
shielded
CHARGING EQUIPMENT FOR ELECTRIC VEHICLES INSTALLATION MANUAL