EasyManua.ls Logo

KSB PumpDrive 2 - Modbus RTU Module Parameters

KSB PumpDrive 2
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Commissioning/Shutdown
131 of 212
PumpDrive 2
NOTE
If the field bus is only used for monitoring purposes, the Control Point parameter
3-6-2 is set to Local.
NOTE
The frequency inverter is reset when a field bus module is replaced or retrofitted.
Menu 3-12 for setting the parameters of the field bus module is then enabled.
Table108: Modbus RTU Module parameters
Parameter Description Possible settings Factory setting
3-6-2 Control Point
Toggling the control point from Local to Field
Bus. DIGIN/ANIN have the highest priority. The
actual value source must be configured
separately.
Local
Field Bus
Local
3-12-2-1 Modbus Slave Address
Modbus slave address of the system
1 - 247 1
3-12-2-2 Baud Rate
Baud rate of the Modbus slave
1200
2400
4800
9600
19200
38400
56k
115k
19200
3-12-2-3 Parity
Parity of the Modbus slave
Even
Odd
No parity
Even
3-12-2-4 Modbus Address Range of Pump
Configurable address range via which the local
parameters of the pump are addressed.
0x0100 - 0x1FF
0x0200 - 0x2FF
0x0300 - 0x3FF
0x0400 - 0x4FF
0x0500 - 0x5FF
0x0600 - 0x6FF
0x0100 - 0x01FF
3-12-2-5 Cycle Time, Setpoint/Control Value
Time delay before the message (warning or
alert) is triggered. In a redundant system, only
a warning is output as the auxiliary master can
assume the function. Only if the setpoint/
control value also fails at the auxiliary master is
the alert output, which then triggers the
specified response to setpoint/control value
failure.
0,0…10,0 s 5,0s
3-12-2-6 Cycle Time, Actual Value
Time delay before the message (warning or
alert) is triggered. In a redundant system, only
a warning is output as the auxiliary master can
assume the function. Only if the actual value
also fails at the auxiliary master is the alert
output, which then triggers the specified
response to actual value failure.
0,0…10,0 s 1,0s

Table of Contents

Other manuals for KSB PumpDrive 2

Related product manuals