EasyManua.ls Logo

KSB PumpDrive 2 - Closed-Loop Control Mode with External Setpoint Signal

KSB PumpDrive 2
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Commissioning/Shutdown
79 of 212
PumpDrive 2
Parameter Description Possible settings Factory setting
3-8-2-2 Analog Input 2 Function
Function of analog input2. Internal
operating values cannot be used as an
actual value source.
Differential Pressure OFF
3-8-2-3 Analog Input 2 Lower Limit 0,00 0,00
3-8-2-4 Analog Input 2 Upper Limit 10,00 100,00
1-3-1 System Start / Stop
This function is used to start the system.
Start Stop
NOTE
The System Start/ Stop parameter (1-3-1) must be set to Stop if the system start
takes place via the digital input.
8.7.1.2.2 Closed-loop control mode with external setpoint signal
The setpoint can be specified via an external setpoint signal. If a setpoint is
simultaneously specified via the control panel, the setpoint via the analog input has a
higher priority (ðSection8.2,Page65) .
NOTE
The parameter values and value ranges/units entered are mutually dependent. This
is why the first step in parameterising the frequency inverter is always to specify the
applicable value range and units (refer to parameter 3-11). If the value range or
unit is subsequently changed, all dependent parameters must be checked for
correctness again.
DI
-
EN
+
2
4
V
GND
DI4
DI
3
D
I
2
DI1
+
2
4V
DICOM1
D
I5
AO
1
-GND
A
O1
A
I
N2 +
+24
V
A
IN
1
+
+
2
4
V
COM2
NO
2
COM1
NC
2
+
2
4
V
+
24V
C
1
C2
C3
C4
C
5
C
6
C7
C8
C9
C
10
B1
B
2
B
3
B
4
B
5
B6
B7
B8
B9
B10
A
1
A
2
A
3
A
4
A
5
A
6
A
7
A8
A9
A
1
0
AIN2 -
A
I
N
1 -
NC1
NO
1
G
N
D
G
N
D
G
N
D
GN
D
2
1 56
34
G
ND
4.
.
.20mA
7
Fig.60: Terminal wiring diagram, closed-loop control mode (dashed line = optional)
1 Start / Stop 2
2 Feedback value transmitter
3 Signal relay 1 (ðSection8.10.3,Page120)
4 Signal relay 2 (ðSection8.10.3,Page120)
5 Digital enable input
6 Ground for digital inputs
7 External setpoint signal
Example
The frequency inverter is to control the system to achieve a setpoint of 6.7bar in a
differential pressure control process. For this purpose, a differential pressure sensor
(4 - 20mA) with a measuring range of 0 to 10bar is connected to analog input 2 of

Table of Contents

Other manuals for KSB PumpDrive 2

Related product manuals