7 Installation at Site
38 of 212
PumpDrive 2
7.4.2.6 Output filter
The maximum cable lengths must be maintained in order to meet RFI suppression
requirements to EN55011. Output filters are required if the maximum cable lengths
are exceeded.
Technical data available on request. (ðSection12.2.8,Page205)
7.4.3 Electrical connection
7.4.3.1 Removing the housing cover
DANGER
Contact with live components
Risk of fatal injury due to electric shock!
▷ Never remove the centre housing part from the heat sink.
▷ Mind the capacitor discharge time.
After switching off the frequency inverter, wait 10minutes until dangerous
voltages have discharged.
The housing cover consists of a C-shaped housing cover panel. The terminals of the
power and motor connection cables are additionally guarded by a protective cover to
prevent them from being touched.
C-shaped housing cover
Fig.17: C-shaped housing cover
1. Remove the cross-recessed head screws on the C-shaped cover.
2. Remove the C-shaped cover.