7 Installation at Site
38 of 212
PumpDrive 2
7.4.2.6 Output filter
The maximum cable lengths must be maintained in order to meet RFI suppression
requirements to EN55011. Output filters are required if the maximum cable lengths
are exceeded.
Technical data available on request. (ðSection12.2.8,Page205)
7.4.3 Electrical connection
7.4.3.1 Removing the housing cover
DANGER
Contact with live components
Risk of fatal injury due to electric shock!
▷ Never remove the centre housing part from the heat sink.
▷ Mind the capacitor discharge time.
After switching off the frequency inverter, wait 10minutes until dangerous
voltages have discharged.
The housing cover consists of a C-shaped housing cover panel. The terminals of the
power and motor connection cables are additionally guarded by a protective cover to
prevent them from being touched.
C-shaped housing cover
Fig.17: C-shaped housing cover
1. Remove the cross-recessed head screws on the C-shaped cover.
2. Remove the C-shaped cover.

Table of Contents