10 Parameter List
PumpDrive 2
183 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-11-7-2 Maximum Current Maximum limit of measuring range 3-11-7-1 … 150,00 A 150,00
3-11-8 Frequency
3-11-8-1 Minimum Frequency Minimum limit of measuring range 0,0 … 3-11-8-2 Hz 0,0
3-11-8-2 Maximum Frequency Maximum limit of measuring range 3-11-8-1 … 200,0 Hz 200,0
3-11-9 Voltage
3-11-9-1 Minimum Voltage Minimum limit of measuring range 0 … 3-11-9-2 V 0
3-11-9-2 Maximum Voltage Maximum limit of measuring range 3-11-9-1 … 1000 V 1000
3-12 Field Bus
3-12-1 Profibus
3-12-1-1 Profibus Slave Address Profibus slave address of the system 1 … 126 126
3-12-1-2 Pump Number Unique assignment of the pump in multiple
pump configuration
1 … 6 1
3-12-2 Modbus
3-12-2-1 Modbus Slave Address Modbus slave address of the system 1…247 1
3-12-2-2 Baud Rate Baud rate of the Modbus slave ▪ 4800
▪ 9600
▪ 19200
▪ 38400
▪ 57600
▪ 115200
19200
3-12-2-3 Parity Parity of the Modbus slave ▪ Even
▪ Odd
▪ No parity
Even
3-12-2-4 Modbus Address Range
of Pump
Configurable address range via which the
local parameters of the pump are addressed
▪ 0x1000 - 0x1FFF
▪ 0x2000 - 0x2FFF
▪ 0x3000 - 0x3FFF
▪ 0x4000 - 0x4FFF
▪ 0x5000 - 0x5FFF
▪ 0x6000 - 0x6FFF
0x1000 - 0x1FFF