10 Parameter List
PumpDrive 2
185 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-12-3-7 Control Direction,
Temperature Control
Specifies the control direction for
temperature control. The control direction
is used if the actual value is supplied via
nviRemoteTemp.
OFF / ON OFF
3-12-3-8 LON Dyn Press Comp
Method
Determines whether dynamic pressure
compensation is used for pressure control
via nviRemotePress.
OFFSpeedFlow Rate OFF
3-13 PumpMeter
3-13-1 Read Out Name Plate Transfers the name plate information from
PumpMeter to PumpDrive
Run
3-13-2 Address Modbus address of PumpMeter device
connected
1 … 247 247
3-13-3 Baud Rate Modbus baud rate of PumpMeter device
connected
▪ 9600
▪ 19200
▪ 38400
▪ 115200
38400
3-13-4 Monitoring Period System bus, Modbus time-out setting 1 … 180 s 15
3-13-5 PumpMeter Master/Slave If PumpMeter is to be used as a redundant
system sensor fitted in the header in dual/
multiple pump configurations or on
EtalineZ pump sets, the parameter must be
set to Master. In all other scenarios, the
parameter is set to Slave.
▪ Slave
▪ Master
Slave
4 Information
4-1 Frequency inverter
4-1-1 Device ID User-defined device name for identifying
the drive. The control panel just allows
read-only access to this parameter. The
device name can only be changed via the
ServiceTool/APP.
4-1-2 Serial Number Serial number of the frequency inverter
4-1-3 Software Version Software version of frequency inverter
4-1-4 Software Revision Revision of frequency inverter software
4-1-5 Device Type Device type of the frequency inverter
4-1-6 Frequency Inverter
Power Class
Setting the power class of the frequency
inverter
Dependent on