Configuration
8200SHB0199
7-61
7.5.15 Indirect torque limitation
Only HVAC” controllers
Code Name Possible settings IMPORTANT
C
o
d
e
N
a
m
e
Lenze Choice Info
I
M
P
O
R
T
A
N
T
C005 -3- Open loop operation via frequency
input E1 with limitation of the
apparent motor current via
terminal 8
C005 = -3-
possible with
C014 = -2-, -4-
Function With C005 = -3-, the apparent motor current (indirect torque limitation) can be limited with an
external signal via the analog input terminal 8. Enter a motor current limit.
Adjustment The influence of the torque limitation is adjusted via the analog input terminal 8
(see chapter 7.5.11.1).
-
The effective current limit is indicated in % in C047.
-
C022 has no influence. The external signal via terminal 8 selects the current limit.
-
C023 remains effective.
Example Constant mass flow control:
8200
air/discharge
heavy
cold
warm
M
f
light
Fan
mass
flow
m = const.